Sensor alarm troubleshooting
133
1Ch +3.3V IPMI Minor voltage high Voltage over 3.47V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 3.63V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 3.8V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 3.14V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 2.97V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
1Dh +3.3V Minor voltage high Voltage over 3.47V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 3.63V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 3.8V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 3.14V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 2.97V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
1Eh +1.8V Minor voltage high Voltage over 1.89V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage high Voltage over 1.98V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage high Voltage over 2.07V threshold;
CPM will not go into M4 state.
1
Remove CPM and contact customer support.
Minor voltage low Voltage under 1.71V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm worsens.
Major voltage low Voltage under 1.62V threshold;
CPM will not go into M4 state.
1
Monitor to see if the alarm is persistent. If persistent,
remove CPM and contact customer support.
Critical voltage low Voltage at 0V threshold; CPM will
not go into M4 state.
1
Remove CPM and contact customer support.
Table 38. Sensor alarms and recommended actions (sheet 9 of 14)
Number Name Alarm level Possible errors or faults Recommendation